No. Name Unit
–
Model CIMR-Po
– 5A0003 5A0004 5A0006 5A0009 5A0011
o2-04 Drive Model Selection Hex. C3 C4 C5 C7
E2-11 Motor Rated Power
kW
(HP)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
L2-04
Momentary Power Loss Voltage Recovery
Time
s 0.5 0.5 0.6 0.7 0.8
L3-24
Motor Acceleration Time for Inertia
Calculations
s 0.166 0.145 0.154 0.168 0.175
L8-02 Overheat Alarm Level °C 110 110 110 110 115
L8-35 Installation Method Selection – 2 2 2 2 2
L8-38 Carrier Frequency Reduction Selection – 2 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10
B.16 Defaults by Drive Model
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
499
B
Parameter List