No. Name Unit Default Settings
–
Model CIMR-Po
– 5A0017 5A0022 5A0027 5A0032
o2-04 Drive Model Selection Hex. CA CC CD CE
E2-11 Motor Rated Power kW (HP)
11
(15)
15
(20)
18.5
(25)
22
(30)
b3-04 V/f Gain during Speed Search % 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
– – – – –
b3-26 Start Speed Search Select – – – – –
b8-03 Energy Saving Control Filter Time Constant s 0.5 0.5 0.5 0.5
b8-04 Energy Saving Coefficient Value – 172 154 140 129
C5-17 Motor Inertia
kgm
2
0.053 0.076 0.138 0.165
C6-02 Carrier Frequency Selection – 7 7 7 7
E2-01 Motor Rated Current A 17 22 27 32
E2-02 Motor Rated Slip Hz 1.7 1.6 1.67 1.7
E2-03 Motor No-Load Current A 5.1 6.6 8.1 9.6
E2-05 Motor Line-to-Line Resistance Ω 1.17 0.9 0.66 0.52
E2-06 Motor Leakage Inductance % 19.6 17.2 20.1 23.5
E2-10 Motor Iron Loss for Torque Compensation W 385 440 508 586
L2-02 Momentary Power Loss Ride-Thru Time s 1 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1.2 1.2 1.2
L2-04 Momentary Power Loss Voltage Recovery Time s 0.9 1 1 1
L3-24 Motor Acceleration Time for Inertia Calculations s 0.27 0.24 0.32 0.36
L8-02 Overheat Alarm Level °C 120 120 115 115
L8-35 Installation Method Selection – 2 2 2 2
L8-38 Carrier Frequency Reduction Selection – 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
B.16 Defaults by Drive Model
500
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual