Drive Model Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0145
R/L1, S/L2, T/L3
95
(3/0)
95 to 150
(2/0 to 300)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
95
(3/0)
95 to 150
(2/0 to 300)
⊖, ⊕1
–
70 to 95
(3/0 to 4/0)
⊕3
–
70 to 95
(1/0 to 2/0)
35
(3)
35 to 150
(3 to 300)
5A0192
R/L1, S/L2, T/L3
185
(300)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
150
(250)
95 to 300
(2/0 to 600)
⊖, ⊕1
–
95 to 185
(2/0 to 400)
⊕3
–
95 to 120
(2/0 to 250)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3
240
(400)
95 to 300
(2/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185
(350)
95 to 300
(2/0 to 600)
⊖, ⊕1
–
95 to 240
(2/0 to 500)
⊕3
–
150
(250 to 300)
M10
18 to 23
(159 to 204)
50
(1)
35 to 300
(1 to 350)
M12
32 to 40
(283 to 354)
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended
by the terminal manufacturer for crimping. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent)
for the insulation cap. Table D.7 matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp
terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge
and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.
Table D.7 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Machine No. Die Jaw
200 V Class
2A0004
2A0006
2A0008
2A0010
14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12
R5.5-4 TP-005 100-054-029
10
2A0012
14 14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12 12
R5.5-4 TP-005 100-054-029
10
2A0018
– 14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12
R5.5-4 TP-005 100-054-029
10
2A0021
12
M4 R5.5-4 YA-4 AD-900 TP-005 100-054-029
10
D.3 UL and CSA Standards
558