ABB ACH580-01 - Guidelines for Installing the Drive to a TT System

ABB ACH580-01
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IT systems (ungrounded or
high-resistance grounded
[>30 ohms]) (C)
Corner-grounded (B1) and
midpoint-grounded delta
systems (B2)
600 V
Symmetrically groun-
ded TN systems (TN-S
systems) ie. center-
grounded wye (A)
Frame
size
Drive Drive
PE
L3
L2
L1
L3
L2
L1
Drive
PE
L3
L2
L1
B1 C
B2
PE
L2
L3
L1
N
Drive
A
1)
Frames R4 and R5 are not evaluated for use on corner-grounded systems or midpoint-grounded delta systems
by IEC standards.
Note: These are the EMC filter and varistor screws of different drive frame sizes.
Ground-to-phase varistor screwsEMC filter screwsFrame size
VAREMC screwR1…R3
R4 v2
VARTwo EMC screwsR4…R5
VARTwo EMC screwsR6…R9
Guidelines for installing the drive to a TT system
The drive can be installed to a TT system under these conditions:
1. Residual current device has been installed in the supply system.
2. These screws have been disconnected. Otherwise EMC filter and ground-to-phase
varistor capacitor leakage current will cause the residual current device to trip.
Electrical installation IEC 117