8. Slide the cables through the holes in the cable entry and attach the grommets to
the holes (the motor cable to the right and the input power cable to the left).
9. Connect the motor cable:
Ground the shield 360 degrees under the grounding clamps.
Connect the twisted shield of the cable to the grounding terminal (9a).
Connect the phase conductors of the cable to terminals T1/U, T2/V and T3/W.
Tighten the screws to the torque given in the table (9b).
Note 1 for frames R8…R9: If you connect only one conductor to the connector,
ABB recommends that you put it under the upper pressure plate. If you use parallel
power cables, put the first conductor under the lower pressure plate and the second
under the upper one.
Note 2 for frames R8…R9: The connectors are detachable but ABB does not
recommend that you detach them. If you do, detach and reinstall the connectors as
described in Detaching and reinstalling the connectors (page 136).
Input power cable
10. Connect the input power cable as in step 9. Use terminals L1, L2, L3.
8
10a
10b
8
M5×25/35
9a
9b
PE,
L1, L2, L3, T1/U, T2/V, T3/WFrame size
lbf·ftN·mlbf·ftN·mlbf·ftN·m
0.91.27.29.82230R6
0.91.27.29.83040R7
0.91.27.29.83040R8
0.91.27.29.85270R9
Detaching and reinstalling the connectors
This is possible but not recommended.
136 Electrical installation IEC