9. Slide the conductors through the conduit.
10. Connect the conductors:
• Connect the grounding conductor to the grounding terminal (10a).
• Connect the phase conductors to terminals T1/U, T2/V and T3/W. Tighten the
screws to the torque given in the table (10b).
PE,
L1, L2, L3, T1/U,
T2/V, T3/W
Frame
size
lbf·ftN·mlbf·ftN·m
7.29.82230R6
7.29.83040R7
7.29.83040R8
7.29.85270R9
Note 1 for frames R8…R9: If you connect only one conductor to the connector,
ABB recommends that you put it under the upper pressure plate. If you use parallel
power cabling, put the first conductor under the lower pressure plate and the second
under the upper one.
Note 2 for frames R8…R9: The connectors are detachable but ABB does not
recommend that you detach them. If you do, detach and reinstall the connectors as
described in Detaching and reinstalling the connectors (page 185).
Input power cabling
11. Repeat steps 8…10 for the conductors. Use terminals L1, L2, L3.