EasyManua.ls Logo

ABB ACH580-01 - Surrounding Air Temperature Derating, IP21 (UL Type 1)

ABB ACH580-01
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Surrounding air temperature derating, IP21 (UL Type 1)
IP21 (UL Type 1) drive types, other than the exceptions below
In the temperature range +40…50 °C (+104…122 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying
the current given in the rating table by the derating factor (k, in the diagram below).
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
0.80
-15 °C
+5°F
0.85
0.95
IP21 (UL Type 1) drive type -078A-4; -099A-6, -125A-6, -144A-6
-078A-4: In the temperature range +40…45 °C (+104…113 °F), the rated output current
is derated by 1% for every added 1 °C (1.8 °F). In the temperature range +45…50 °C
(+113…122 °F), the rated output current is derated by 2% for every added 1 °C (1.8
°F). The output current can be calculated by multiplying the current given in the rating
table by the derating factor (k):
0.90
k
0.80
0.75
0.85
0.95
T
+40 °C
+104 °F
+50 °C
+122 °F
+45 °C
+113 °F
1.00
-15 °C
+5 °F
0.85
-099A-6, -125A-6, -144A-6: In the temperature range +40…45 °C (+104…113 °F), the
rated output current is not derated at all. In the temperature range +45…50 °C
(+113…122 °F), the rated output current is derated by 1% for every added 1 °C (1.8 °F).
242 Technical data

Table of Contents

Other manuals for ABB ACH580-01

Related product manuals