Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
TWire sizeTWire size
N·mmm
2
N·mmm
2
mmpcs
0.5…0.60.14…1.50.5…0.60.2…2.5173R2
0.5…0.60.14…1.50.5…0.60.2…2.5173R3
0.5…0.60.14…1.50.5…0.60.2…2.5173R5
0.5…0.60.14…1.50.5…0.60.14…2.5174R6
0.5…0.60.14…1.50.5…0.60.14…2.5174R7
0.5…0.60.14…1.50.5…0.60.14…2.5174R8
3-phase U
n
= 400 or 480 V
0.5…0.60.14…1.50.5…0.60.2…2.5173R1
0.5…0.60.14…1.50.5…0.60.2…2.5173R2
0.5…0.60.14…1.50.5…0.60.2…2.5173R3
0.5…0.60.14…1.50.5…0.60.2…2.5174R4
0.5…0.60.14…1.50.5…0.60.2…2.5173R5
0.5…0.60.14…2.50.5…0.60.14…2.5174R6
0.5…0.60.14…2.50.5…0.60.14…2.5174R7
0.5…0.60.14…2.50.5…0.60.14…2.5174R8
0.5…0.60.14…2.50.5…0.60.14…2.5174R9
■ UL (NEC)
Control cable entries, wire sizes and tightening torques (T) are given below.
Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
TWire sizeTWire size
lbf·ftAWGlbf·ftAWGinpcs
3-phase U
1
= 200…240 V, P
n
at U
n
= 208/230 V, 60 Hz
0.426…160.424…140.673R1
0.426…160.424…140.673R2
0.426…160.424…140.673R3
0.426…160.424…140.674R4
0.426…160.424…140.673R5
0.426…160.426…140.674R6
0.426…160.426…140.674R7
0.426…160.426…140.674R8
0.426…140.426…140.674R9
Technical data 285