Frame sizeOutput ratingsInput ratingACH580-
01-
Light-duty useMax. current
P
Ld
I
Ld
I
max
I
1
hpAAA
R9250242346242242A-6
R9250271411271271A-6
Definitions
Nominal output voltage of the drive. For input voltage range [U
1
, see section
Electrical power network specification (page 286). 50 Hz for IEC ratings and
U
n
60 Hz for UL (NEC) ratings.
Nominal input current. Continuous rms input current (for dimensioning cables and
fuses).
I
1
Maximum output current. Available for two seconds at start.I
max
Maximum current with 10% overload, allowed for one minute every ten minutes.I
Ld
Typical motor power in light-duty use (10% overload). The horsepower (hp)P
Ld
ratings apply to most NEMA 4-pole motors.
Maximum current with 50% overload, allowed for one minute every ten minutes.
Hd
1)
Maximum current with 40% overload, allowed for one minute every ten minutes.
Typical motor power in heavy-duty use (50% overload).
Hd
■ Conversion tables for IEC and North American type codes
Frame sizeNorth American type
ACH580-01
IEC type
ACH580-01
3-phase U
n
= 230 V
R104A6-204A7-2
R106A6-206A7-2
R107A5-207A6-2
R110A6-2012A-2
R1017A-2018A-2
R2024A-2025A-2
R2031A-2032A-2
R3046A-2047A-2
R3059A-2060A-2
R4075A-2-
R5088A-2089A-2
R5114A-2115A-2
R6143A-2144A-2
R7169A-2171A-2
238 Technical data