AI cable type
1)
,
2)
Cu cable type
1)
Frame sizeACH580-01-
mm
2
mm
2
-3×10 + 10R3033A-4
-3×10 + 10R3039A-4
-3×10 + 10R3046A-4
-3×25 + 16R4062A-4
-3×35 + 16R4073A-4
-3×50 + 25R4 v2089A-4
-3×50 + 25R5088A-4
-3×70 + 35R5106A-4
-3×95 + 50R6145A-4
-3×120 + 70R7169A-4
-3×150 + 70R7206A-4
-2×(3×70+35)R8246A-4
-2×(3×95+50)R8293A-4
-2×(3×120+70)R9363A-4
-2×(3×150+70)R9430A-4
1)
The cable sizing is based on max. 6 cables laid on a cable ladder side by side, ambient temperature 30 °C,
PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364- 5-52/2001). For other conditions,
size the cables according to local safety regulations, appropriate input voltage and the load current of the
drive. See page 278 for the accepted cable sizes of the drive.
2)
Aluminum cables can be used with U
n
= 230 V frames R5…R8 only.
Temperature: For IEC, select a cable rated for at least 70 °C maximum permissible
temperature of conductor in continuous use. For North America, power cables must be
rated for 90 °C (194 °F) or higher.
Note: For drives with option +B056 (IP55, UL Type 12), select a cable rated for at least
90 °C (194 °F) maximum permissible temperature of conductor in continuous use.
Voltage: 600 V AC cable is accepted for up to 500 V AC.
Terminal and entry data for the control cables
■ IEC
Control cable entries, wire sizes and tightening torques (T) are given below.
Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
TWire sizeTWire size
N·mmm
2
N·mmm
2
mmpcs
3-phase U
n
= 230 V
0.5…0.60.14…1.50.5…0.60.2…2.5173R1
284 Technical data