ABB ACH580-01 - Finalization; Connection Procedure, Frame R5; IP21 (UL Type 1); IP55 (UL Type 12)

ABB ACH580-01
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12. Connect the grounding conductor to the grounding terminal (12a) and the other
conductors to the R+ and R- terminals (12b). Tighten the screws to the torque given
in the table.
R3R1…R2
BRAKE RESINPUT
PE
MOTOR
R-
R+
UDC+
L1 L2 L3 T1/U T2/V T3/W
12a
12b
MOTOR
T1
U
T2
V
T3
W
INPUT
L1 L2 L3
BRAKE RES
R-R+
UDC+
12a
12b
R3R2R1Frame size
lbf·ftN·mlbf·ftN·mlbf·ftN·m
2.63.51.11.50.71.0R+, R-
1.11.51.11.51.11.5
PE,
Finalization
Note: Frame R1: You have to install any optional I/O extension module, if used, in
options slot 2 at this point. See section Installing option modules (page 201).
13. Secure the conduits outside the unit mechanically.
Connection procedure, frame R5
IP21 (UL Type 1)
1. Remove the module cover: Loosen the retaining screws with a T20 Torx screwdriver
(1a) and lift the cover from the bottom outwards (1b) and then up (1c).
Remove the box cover: Loosen the retaining screws with a screwdriver (1d) and
slide the cover downwards (1e).
IP55 (UL Type 12)
1. Remove the front cover: Loosen the retaining screws with a T20 Torx screwdriver
(1a) and lift the cover from the bottom outwards (1b) and then up (1c).
178 Electrical installation North America