10
Technical data
Contents of this chapter
This chapter contains the technical specifications of the drive including the ratings, sizes
and technical requirements, provisions for fulfilling the requirements for CE, UL and
other approval marks.
Ratings
■ IEC
FrameOutput ratingsInput
rating
ACH580-
01-
Heavy-duty useLight-duty useNominal useMax.
current
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
kWAkWAkWAAA
3-phase U
n
= 230 V
R10.553.50.754.60.754.76.34.704A7-2
R10.754.61.16.61.16.78.96.706A7-2
R11.16.61.57.51.57.611.97.607A6-2
R12.27.53.011.83.012.019.112.0012A-2
R13.010.64.016.74.016.922.016.9018A-2
R24.016.75.524.25.524.532.724.5025A-2
R25.524.27.530.87.531.243.631.2032A-2
R37.530.81146.21146.762.446.7047A-2
R31146.21559.4156083.260060A-2
R518.574.82288228913589089A-2
Technical data 231