Frame
size
Air flow (with flange kit)Heat dissipation (with
flange kit)
ACH580-
01-
FrontHeatsinkFrontHeatsink
CFMm
3
/hCFMm
3
/hWW
R4TBATBATBATBA127729052A-4
R4 v2TBATBATBATBA105686052A-4
R4TBATBATBATBA151947065A-4
R4 v2TBATBATBATBA118752065A-4
R4 v2TBATBATBATBA151887077A-4
R5TBATBATBATBA141977078A-4
R5TBATBATBATBA1651099096A-4
R631522564351881733124A-4
R744752654502231758156A-4
R744752654502662464180A-4
R8711203245503262743240A-4
R8711203245503913601260A-4
R9TBATBATBATBA3402849302A-4
R910017067711505244220361A-4
R910017067711506235330414A-4
Terminal and entry data for the power cables
■ IEC
Input, motor , resistor and DC cable entries, maximum wire sizes (per phase) and
terminal screw sizes and tightening torques (T) are given below.
Grounding terminalsL1, L2, L3, T1/U, T2/V, T3/W terminalsCable
entries
Frame
size
TMax wire sizeTMax wire size
(solid/stranded)
Min wire size
(solid/stran-
ded)
2)
Ø
1)
Per
cable
type
N·mmm
2
N·mmm
2
mm
2
mmpcs
3-phase U
n
= 230 V
1.516/161.06/40.2/0.2301R1
1.516/161.516/160.5/0.5301R2
1.535/353.535/250.5/0.5301R3
2.2-5.6706451R5
9.81803015025451R6
9.81804024095541R7
9.8180402×1502×50452R8
3-phase U
n
= 400 or 480 V
278 Technical data