Screwdrivers for the terminals of the main circuitFrame size
Combo: Slot 4.5 mm and PH2R2
PH2R3, R4
Power cables
Typical power cable sizes, IEC
The table below gives copper cable types with concentric copper shield for the drives
with nominal current. The value separated by the plus sign means the diameter of the
PE conductor.
See page 278 for the cable entry sizes allowed for the selected drive frame size.
AI cable type
1)
,
2)
Cu cable type
1)
Frame sizeACH580-01-
mm
2
mm
2
3-phase U
n
= 230 V
-3×1.5 + 1.5R104A7-2
-3×1.5 + 1.5R106A7-2
-3×1.5 + 1.5R107A6-2
-3×1.5 + 1.5R1012A-2
-3×2.5 + 2.5R1018A-2
-3×4.0 + 4.0R2025A-2
-3×6.0 + 6.0R2032A-2
-3×10 + 10R3047A-2
-3×16 + 16R3060A-2
3×50 + 253×35 + 16R5089A-2
3×70 + 353×50 + 25R5115A-2
3×120 + 703×70 + 35R6144A-2
3×150 + 703×95 + 50R7171A-2
3×240 + 1203×120 + 70R7213A-2
2×(3×95 + 50)2×(3×70 + 35)R8276A-2
3-phase U
n
= 400 V
-3×1.5 + 1.5R102A7-4
-3×1.5 + 1.5R103A4-4
-3×1.5 + 1.5R104A1-4
-3×1.5 + 1.5R105A7-4
-3×1.5 + 1.5R107A3-4
-3×2.5 + 2.5R109A5-4
-3×2.5 + 2.5R112A7-4
-3×2.5 + 2.5R2018A-4
-3×6 + 6R2026A-4
Technical data 283