R+, R-, UDC+ and UDC- terminalsCable entriesFrame
size
T
Wire range size (stranded/solid)
2)
Ø
1)
Per cable
type
lbf·ftScrew/BoltMaxMin
AWGAWGinpcs
3-phase U
1
= 200…240 V, P
n
at U
n
= 208/230 V, 60 Hz
0.7
3)
10240.911R1
1.1
3)
6200.911R2
2.6
3)
2201.181R3
3.0
3)
1501.541R4
4.1M52/10101.541R5
22.1M8300 MCM41.771R6
29.5M10500 MCM3/102.131R7
29.5M102×300 MCM2×1/01.772R8
51.6M122×500 MCM2×3/02.132R9
3-phase U
1
= 440…480 V, P
n
at U
n
= 480 V, 60 Hz
0.7
3)
10240.911R1
1.1
3)
6200.911R2
2.6
3)
2200.911R3
3.0
3)
1501.541R4
4.1M52/10101.541R5
22.1M8300 MCM41.771R6
29.5M10500 MCM3/02.131R7
29.5M102×300 MCM2×1/01.772R8
51.6M122×500 MCM2×3/02.132R9
3-phase U
1
= 525…600 V, P
n
at U
n
= 575 V, 60 Hz
1.1
3)
6200.911R2
2.6
3)
2201.181R3
4.1M52/0101.541R5
29.5M10500 MCM3/02.131R7
29.5M102×300 MCM2×1/01.772R8
51.6-2×500 MCM2×3/02.132R9
1)
Maximum cable diameter accepted. For the entry plate hole diameters, see chapter Dimension
drawings (page 309).
2)
Note: Minimum wire size does not necessarily have enough current capability for full load.Make sure the
installation complies with local laws and regulations.
3)
See the table below
Screwdrivers for the terminals of the main circuitFrame size
Combo: Slot 4 mm and PH1R1
282 Technical data