Grounding terminalsL1, L2, L3, T1/U, T2/V, T3/W terminalsCable
entries
Frame
size
TWire range (stranded/sol-
id)
T
Wire range (stranded/solid
2)
Ø
1)
Per
cable
type
MaxMinMaxMin
lbf·ftAWGAWGlbf·ftAWGAWGinpcs
1.1350 MCM
3)
29.5500 MCM3/02.131R7
1.12×350 MCM
3)
29.52×300 MCM2×1/01.772R8
7.22×350 MCM
3)
51.62×500 MCM2×3/02.132R9
3-phase U
1
= 440…480 V, P
n
at U
n
= 480 V, 60 Hz
1.16180.710241.181R1
1.16181.16201.181R2
1.12242.62201.181R3
2.12123.01201.771R4
1.6
3)3)
4.12/0101.771R5
7.2350 MCM
3)
22.1300 MCM41.771R6
7.2350 MCM
3)
29.5500 MCM3/02.131R7
7.22×350 MCM
3)
29.52×300 MCM2×1/01.772R8
7.22×350 MCM
3)
51.62×500 MCM2×3/02.132R9
3-phase U
1
= 525…600 V, P
n
at U
n
= 575 V, 60 Hz
1.16181.16201.181R2
1.16182.62201.181R3
1.6
3)3)
4.12/0101.771R5
7.2350 MCM
3)
29.5500 MCM3/02.131R7
7.22×350 MCM
3)
29.52×300 MCM2×1/01.772R8
7.22×350 MCM
3)
51.62×500 MCM2×3/02.132R9
1)
Maximum cable diameter accepted. For the entry plate hole diameters, see chapter Dimension
drawings (page 309).
2)
Note: Minimum wire size does not necessarily have enough current capability for full load.Make sure the
installation complies with local laws and regulations.
3)
Either cable lug, not provided (R5) or cable clamp (R6…R9) is used for grounding.
Note: For the tightening torques of the grounding terminals, see sections Connection
procedure, frames R1…R4 (page 174), Connection procedure, frame R5 (page 178) and
Connection procedure, frames R6…R9 (page 182).