uR or aR (DIN 43653 bolted tags)Input
current
Min.
short-
circuit
current
1)
ACH580-
01-
IEC 60269
size
Buss-
mann type
Voltage
rating
I
2
tNominal
current
VA
2
sAAA
0170M1318690850012573480073A-4
0170M13196901600016088700089A-4
0170M13196901600016088700088A-4
1170M301569015000200106700106A-4
1170M3016690285002501451000145A-4
1170M3017690465003151691280169A-4
1170M3018690685003502061520206A-4
2170M50096901050004502463010246A-4
2170M50106901450005002934000293A-4
2170M50126902750006303635550363A-4
2170M50136904050007004307800430A-4
1)
Minimum short-circuit current of the installation
Circuit breakers (IEC)
This section does not apply to the North American market. See section Circuit breakers
(UL).
The protective characteristics of circuit breakers depend on the type, construction and
settings of the breakers. There are also limitations pertaining to the short-circuit capacity
of the supply network.
WARNING!
Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases can escape from the breaker
enclosure in case of a short-circuit. To make sure of safe use, pay special attention
to the installation and placement of the breakers. Obey the manufacturer’s
instructions.
You can use the circuit breakers listed below. Other circuit breakers can be used with
drive if they provide the same electrical characteristics. ABB does not assume any
liability whatsoever for the correct function and protection with circuit breakers not listed
below. Furthermore, if the recommendations given by ABB are not obeyed, the drive
can experience problems that the warranty does not cover.
Technical data 257