The minimum short-circuit power Sce given for each drive type
for the Rsce (transformer short circuit ratio) value of 350.
Minimum short-circuit power
(IEC/EN 61000-3-12)
Frame
size
Min. short circuit
power
Input rat-
ing
ACH580-
01
480 V400 V
SscSscI
1
MVAMVAA
3-phase U
n
= 400 V and 480 V, IEC ratings
R10.60.62.602A7-4
R10.90.83.303A4-4
R11.01.04.004A1-4
R11.41.45.605A7-4
R11.81.87.207A3-4
R12.22.39.409A5-4
R13.53.112.612A7-4
R24.14.117.0018A-4
R26.76.125.0026A-4
R37.97.832.0033A-4
R39.99.238.0039A-4
R312.810.945.0046A-4
R415.115.062062A-4
R418.917.773073A-4
R4 v222.421.689089A-4
R522.421.388088A-4
R527.925.7106106A-4
R636.135.2145145A-4
R745.441.0169169A-4
R752.450.0206206A-4
R869.859.7246246A-4
R875.771.1293293A-4
R9105.188.0363363A-4
R9120.5104.3430430A-4
Motor connection data
Asynchronous AC induction motors, permanent magnet motors
and synchronous reluctance motors
Motor types
The drive provides solid state short circuit protection for the
motor connection per IEC/EN 61800-5-1 and UL 61800-5-1.
Short-circuit current protection
(IEC/EN 61800-5-1)
0…500 Hz. This is indicated in the type designation label as
output frequency level f
1
(0…500 Hz).
Frequency (f
2
)
288 Technical data