0.01 HzFrequency resolution
See section Ratings (page 231).
Current
2 kHz, 4 kHz (default), 8 kHz, 12 kHzSwitching frequency
Operational functionality and motor cable lengthMaximum recommended motor
cable length The drive is designed to operate with optimum performance
with the following maximum motor cable lengths.
Note: Conducted and radiated emissions of these motor cable
lengths do not comply with EMC requirements.
Maximum motor cable length, 4 kHzFrame
size
Vector controlScalar control
ftmftm
Standard drive, without external options
330100330100R1
660200660200R2*
990300990300R3*
990300990300R4
990300990300R5
990300990300R6
990300990300R7
990300990300R8
990300990300R9
*For 600 V drives the maximum motor cable length is 100 m
(330 ft) for frame R2 and 200 m (660 ft) for frame R3.
Note:
1. In multimotor systems, the calculated sum of all motor cable
lengths must not exceed the maximum motor cable length
given in the table.
2. Longer motor cables cause a motor voltage decrease which
limits the available motor power. The decrease depends
on the motor cable length and characteristics. Contact your
local ABB representative for more information.
3. When using longer motor cables than 50 m (165 ft), 8 and
12 kHz switching frequencies are not allowed. With motor
cable length over 100 m, disconnect EMC DC screw if ap-
plicable.
4. Acceptable motor cable length for motor manufactures may
be different. Check with specific motor manufacturer for
maximum allowable distance.
Technical data 289