Control cable entries and terminal sizesCable entriesFrame
size
DI, AI/O, AGND, RO, STO
terminals
+24V, DCOM, DGND, EXT.
24V terminals
Max cable
size
Holes
TWire sizeTWire size
lbf·ftAWGlbf·ftAWGinpcs
3-phase U
1
= 440…480 V, P
n
at U
n
= 480 V, 60 Hz
0.426…160.424…140.673R1
0.426…160.424…140.673R2
0.426…160.424…140.673R3
0.426…160.424…140.674R4
0.426…160.424…140.673R5
0.426…140.426…140.674R6
0.426…140.426…140.674R7
0.426…140.426…140.674R8
0.426…140.426…140.674R9
3-phase U
1
= 525…600 V, P
n
at U
n
= 575 V, 60 Hz
0.426…160.424…140.673R2
0.426…160.424…140.673R3
0.426…160.424…140.673R5
0.426…160.426…140.674R7
0.426…160.426…140.674R8
0.426…160.426…140.674R9
Electrical power network specification
• ACH580-01-xxxx-2 drives: Input voltage range 3~ 208…240
V AC +10%…. -15%.
IEC: This is indicated in the type designation label as typical
input voltage levels 3~ 230 V AC.
North America: This is indicated in the type designation label
as typical input voltage levels 1~ 208/230 V AC and 3~
208/230 V AC.
• ACH580-01-xxxx-4 drives: Input voltage range 3~ 380…480
V AC +10%…-15%.
This is indicated in the type designation label as typical input
voltage levels 3~ 400/480 V AC.
• ACH580-01-xxxx-6 drives: Input voltage range 3~ 525…600
V AC +10%…-15%.
This is indicated in the type designation label as typical input
voltage level 3~ 600 V AC.