EasyManua.ls Logo

ABB ACH580-01 - Connecting the Power Cables; Connection Diagram

ABB ACH580-01
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connecting the power cables
Connection diagram
L1 L2 L3
T1/U T2/V T3/W
UDC+
R+R-
L1 L2 L3(PE) (PE)PE
PE
U1
V1
W1
3 ~ M
1
2a
2b
3
5
6a
4
3
7
6b
ACH580-01
For alternatives, see Selecting the main supply disconnecting device (page 87)
1
With a conduit: Use a separate grounding PE cable (2a) or a PE conductor (2b) inside the
conduit if the conductivity of the conduit does not meet the requirements for the PE conductor
(see General guidelines (page 96).
2
With a shielded cable: Use a separate grounding PE cable (2a) or a cable with a separate
PE conductor (2b) if the conductivity of the shield does not meet the requirements for the
PE conductor (see General guidelines (page 96)).
Note: If the cross-section of the Cu PE conductor is less than 8 AWG, install a second Cu
PE conductor of the same cross-sectional area as the original PE conductor. Alternatively,
you can use a Cu PE conductor with at least 10 mm
2
cross-section. See page 24.
With the conduit: Make sure of a proper grounding of the conduit at the cable entry. Ground
the other end of the conduit and PE conductor (if used) at the distribution board.
3
With a shielded cable: Do a 360-degree grounding if shielded cable is used. Ground the
other end of the input cable shield and PE conductor (if used) at the distribution board.
With the conduit: Make sure of a proper grounding of the conduit at the cable entry.4
With a shielded cable: Do a 360-degree grounding of the shield.
172 Electrical installation North America

Table of Contents

Other manuals for ABB ACH580-01

Related product manuals