Grounding terminalsL1, L2, L3, T1/U, T2/V, T3/W terminalsCable
entries
Frame
size
TMax wire sizeTMax wire size
(solid/stranded)
Min wire size
(solid/stran-
ded)
2)
Ø
1)
Per
cable
type
N·mmm
2
N·mmm
2
mm
2
mmpcs
1.516/161.06/40.20/0.25301R1
1.516/161.516/160.5/0.5301R2
1.535/353.535/250.5/0.5301R3
2.935/354.0500.5/0.5451R4
2.935/355.5701.5/1.5451R4 v2
2.2
35/35
3)
5.6706451R5
9.8
185
3)
3015025451R6
9.8
185
3)
4024095541R7
9.8
2×185
3)
402×1502×50452R8
9.8
2×185
3)
702×2402×95542R9
1)
Maximum cable diameter accepted. For the entry plate hole diameters, see chapter Dimension
drawings (page 309).
2)
Note: Minimum wire size does not necessarily have enough current capability for full load. Make sure the
installation complies with local laws and regulations.
3)
Note: Either cable lug (R5, see page 133) or clamp (R6…R9, see page 136) is used for grounding.
Note: For the tightening torques of the grounding terminals, see sections Connection
procedure, frames R1…R4 (page 123), Connection procedure, frame R5 (page 129) and
Connection procedure, frames R6…R9 (page 134).
R+, R-, UDC+ and UDC- terminalsCable entriesFrame
size
T (Wire screw)Max wire size
(solid/stranded)
Min wire size
(solid/stran-
ded)
2)
Ø
1)
Per cable
type
N·mScrew/Boltmm
2
mm
2
mmpcs
3-phase U
n
= 230 V
10
3)
6/40.2/0.2231R1
1.5
3)
16/160.5/0.5231R2
3.5
3)
35/350.5/0.5301R3
5.6M5706391R5
30M815025451R6
30M1024095541R7
40M102×1502×50452R8
3-phase U
n
= 400 or 480 V
1.0
3)
6/40.20/0.25231R1
Technical data 279