WARNING!
If you install the drive on any other system than symmetrically grounded TN-S
system, see Grounding system compatibility check (page 115) if you have to
disconnect the EMC filter and ground-to-phase varistor.
2. Attach the residual voltage warning sticker in the local language next to the control
unit.
3. Remove the shroud on the power cable terminals by releasing the clips with a
screwdriver (3a) and pulling the shroud out (3b).
Motor cable
Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE
conductor for drive or motor, make sure that is has sufficient conductivity for the
PE.
4. Cut an adequate hole into the rubber grommet. Slide the grommet onto the cable.