Note:
Leave the other ends of the control cable shields unconnected or ground them
indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V.
The shield can also be grounded directly at both ends if they are in the same ground
line with no significant voltage drop between the end points.
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting
the wire with its return wire reduces disturbances caused by inductive coupling.
196 Electrical installation North America