ABB circuit breakerDrive
volume
Enclosure
minimum
volume
CB
voltage
CB
maximum
current
Input
current
Frame
size
ACH580-
01
65 kA @ 240 Vin
3
in
3
VAA
XT2Nαβ100#********1011648024010059.4R3059A-2
XT2Nαβ100#********1669648024010074.8R4075A-2
XT4Nαβ150#********2030810024015088.0R5088A-2
XT4Nαβ150#********20308100240150114R5114A-2
XT4Nαβ200#********2880¤240200143R6143A-2
XT5Nαβ30A#********3369¤240300169R7169A-2
XT5Nαβ30A#********3369¤240300211R7211A-2
XT5Nαβ40A#********3858¤240400273R8273A-2
¤ Enclosure minimum volume is not applicable
See notes 1-11 below
Maximum
I
peak
Maximum
I
2
t
ABB circuit breakerDrive
volume
Enclos-
ure
minim-
um
volume
CB
voltage
CB
maxim-
um cur-
rent
Input
current
Frame
size
ACH580-
01
kA
A
2
s
65 kA @ 240 V
in
3
in
3
VAA
3-phase U
1
= 440…480 V, P
n
at U
n
= 480 V, 60 Hz
23.2
0.512×10
6
XT2Hαβ020#********5066480480202.1R102A1-4
23.2
0.512×10
6
XT2Hαβ020#********5066480480203.0R103A0-4
23.2
0.512×10
6
XT2Hαβ020#********5066480480203.5R103A5-4
23.2
0.512×10
6
XT2Hαβ020#********5606480480204.8R104A8-4
23.2
0.512×10
6
XT2Hαβ020#********5066480480207.6R107A6-4
23.2
0.512×10
6
XT2Hαβ020#********50664804802012.0R1012A-4
23.2
0.512×10
6
XT2Hαβ035#********684162004803514.0R2014A-4
23.2
0.512×10
6
XT2Hαβ035#********684162004803523.0R2023A-4
23.2
0.512×10
6
XT2Hαβ070#********1011277204807027.0R3027A-4
23.2
0.512×10
6
XT2Hαβ070#********1011277204807034.0R3034A-4
23.2
0.512×10
6
XT2Hαβ070#********1011277204807044.0R3044A-4
23.2
0.512×10
6
XT2Hαβ125#********16693024048012552R4052A-4
23.2
0.512×10
6
XT2Hαβ125#********16693024048012565R4065A-4
23.2
0.512×10
6
XT2Hαβ125#********16693024048012577R4077A-4
30
0.98×10
6
XT4Hαβ150#********20303024048015078R5078A-4
30
0.98×10
6
XT4Hαβ150#********20303024048015096R5096A-4
30
0.98×10
6
XT4Hαβ225#********288053705480225124R6124A-4
30
0.98×10
6
XT4Hαβ250#********336953703480250156R7156A-4
30
0.98×10
6
XT4Hαβ250#********336953703480250180R7180A-4
262 Technical data