Note:
1. For the actual degree of protection that can be achieved with flange for each frame
size (on the back and front sides of the drive), see Flange mounting kit installation
supplement (3AXD50000019100 [English]).
2. Regarding flange mounting:
• The outside of the cabinet sets the limit for vertical positioning, since that is
where the cooling is required
• There are no limitations inside the cabinet; practically the outside positioning
defines the distance between drives
• The space inside the cabinet can be used as long as the following requirements
are still met:
• Heat loss dissipation inside the cabinet per the hardware manual
• Sufficient space for the maintenance operations
• Wire bending radius rules according to UL when planning routing for mains
and motor cables.
Free space, IP21 (UL Type 1)Frame
size
Vertical mounting side by sideVertical mounting stand alone
Between
Below
1)
AboveBesideBelowAbove
inmminmminmminmminmminmm
007.872007.872005.911503.39865.91150R1
007.872007.872005.911503.39865.91150R2
007.872007.872005.911502.09537.87200R3
007.872007.872005.911507.872002.0953R4
007.872007.872005.911507.872003.94100R5
0011.83007.872005.9115011.83006.10155R6
0011.83007.872005.9115011.83006.10155R7
0011.83007.872005.9115011.83006.10155R8
0011.83007.872005.9115011.83007.87200R9
1)
Free space below is always measured from the drive frame, not from the cable box.
Free space, IP21 (UL Type 1)
1)
Frame
size
Horizontal mounting
Between
2)
Below
2)
,
3)
Above
2)
inmminmminmm
1.18/7.8730/2003.39865.91150R1