Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of digital inputs and relay outputs.Standard DI, RO10
- / uint16Displays the electrical status of digital inputs DIIL and
DI6…DI1. The activation/deactivation delays of the inputs
DI status10.1
(if any are specified) are ignored. A filtering time can be
defined by parameter 10.51 DI filter time.
Bits 0…5 reflect the status of DI1…DI6; bit 15 reflects the
status of the DIIL input. Example: 1000000000010011b =
DIIL, DI5, DI2 and DI1 are on, DI3, DI4 and DI6 are off.
This parameter is read-only.
- / uint16Displays the status of digital inputs DIIL and DI6…DI1.
This word is updated only after activation/deactivation
DI delayed status10.2
delays (if any are specified). A filtering time can be defined
by parameter 10.51 DI filter time.
Bits 0…5 reflect the delayed status of DI1…DI6; bit 15
reflects the delayed status of the DIIL input.
This parameter is read-only.
- / uint16The electrical statuses of the digital inputs can be
overridden for eg. testing purposes. A bit in parameter 10.4
DI force selection10.3
DI force data is provided for each digital input, and its value
is applied whenever the corresponding bit in this parameter
is 1.
1 = Force DI1 to value of bit 0 of parameter 10.4 DI force
data.
DI1b0
1 = Force DI2 to value of bit 1 of parameter 10.4 DI force
data.
DI2b1
1 = Force DI3 to value of bit 2 of parameter 10.4 DI force
data.
DI3b2
1 = Force DI4 to value of bit 3 of parameter 10.4 DI force
data.
DI4b3
1 = Force DI5 to value of bit 4 of parameter 10.4 DI force
data.
DI5b4
1 = Force DI6 to value of bit 5 of parameter 10.4 DI force
data.
DI6b5
Reservedb6…14
1 = Force DIIL to value of bit 15 of parameter 10.4 DI force
data.
DIILb15
1 = 10000h…FFFFh
- / uint16Contains the values that the digital inputs are forced to
when selected by 10.3 DI force selection.
DI force data10.4
Bit 0 is the forced value for DI1; bit 15 is the forced value
for the DIIL input.
Parameters 175