Settings and diagnostics
Parameters: 31.12 Autoreset selection31.16 Delay time (page 333).
Other programmable protection functions
External events (parameters 31.0131.10)
Five different event signals from the process can be connected to selectable inputs to
generate trips and warnings for the driven equipment. When the signal is lost, an external
event (fault, warning, or a mere log entry) is generated. The contents of the messages
can be edited on the control panel by selecting Menu - Settings - Edit texts.
Motor phase loss detection (parameter 31.19)
The parameter selects how the drive reacts whenever a motor phase loss is detected.
Earth (Ground) fault detection (parameter 31.20)
The earth fault detection function is based on sum current measurement. Note that
an earth fault in the supply cable does not activate the protection
in a grounded supply, the protection activates within 2 milliseconds
in an ungrounded supply, the supply capacitance must be 1 microfarad or more
the capacitive currents caused by shielded motor cables up to 300 meters will not
activate the protection
the protection is deactivated when the drive is stopped.
Safe torque off detection (parameter 31.22)
The drive monitors the status of the Safe torque off input, and this parameter selects
which indications are given when the signals are lost. (The parameter does not affect
the operation of the Safe torque off function itself). For more information on the Safe
torque off function, see the Hardware manual.
Swapped supply and motor cabling (parameter 31.23)
The drive can detect if the supply and motor cables have accidentally been swapped
(for example, if the supply is connected to the motor connection of the drive). The
parameter selects if a fault is generated or not. Note that the protection should be
disabled in drive/inverter hardware supplied from a common DC bus.
Stall protection (parameters 31.2431.28)
The drive protects the motor in a stall situation. It is possible to adjust the supervision
limits (current, frequency and time) and choose how the drive reacts to a motor stall
condition.