Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of I/O extension module 1.I/O extension
module 1
14
See also section Programmable I/O extensions (page 33).
Note: The contents of the parameter group vary according
to the selected I/O extension module type.
None / uint16Activates (and specifies the type of) I/O extension module
1.
Module 1 type14.1
Note: This parameter cannot be changed while the drive
is running.
0Inactive.None
1FIO-01.FIO-01
2FIO-11.FIO-11
4FAIO-01.FAIO-01
3FDIO-01.FDIO-01
1 / uint16Specifies the slot (1…3) on the control unit of the drive into
which the I/O extension module is installed. Alternatively,
Module 1 location14.2
specifies the node ID of the slot on an FEA-03 extension
adapter.
Note: This parameter cannot be changed while the drive
is running.
1 = 1 / 1 = 1Slot 1 = 1; Slot 2 = 2; Slot 3 = 3.
4…254: Node ID of the slot on the FEA-03 extension
adapter.
1...254
No option / uint16Displays the status of I/O extension module 1.Module 1 status14.3
0No module detected in the specified slot.No option
1A module has been detected but cannot be communicated
with.
No communication
2The module type is unknown.Unknown
15An FIO-01 module has been detected and is active.FIO-01
20An FIO-11 module has been detected and is active.FIO-11
24An FAIO-01 module has been detected and is active.FAIO-01
- / uint16
(Visible when 14.1 Module 1 type = FDIO-01)
Displays the status of the digital inputs on the extension
module. The activation/deactivation delays (if any are
DI status14.5
specified) are ignored. A filtering time (for input mode) can
be defined by parameter 14.8 DI filter time.
Bit 0 indicates the status of DI1.
Note: The number of active bits in this parameter depends
on the number of digital input/outputs on the extension
module.
Example: 0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
Parameters 199