Overspeed protection (parameter 31.30)
The user can set overspeed limits by specifying a margin that is added to the
currently-used maximum and minimum speed limits.
Ramp stop supervision (parameters 31.32, 31.33, 31.37 and 31.38)
The control program has a supervision function for both the normal and emergency stop
ramps. The user can either define a maximum time for stopping, or a maximum deviation
from the expected deceleration rate. If the drive fails to stop in the expected manner, a
fault is generated and the drive coasts to a stop.
Main cooling fan supervision (parameter 31.35)
The parameter selects how the drive reacts to a loss of the main cooling fan.
With an inverter unit consisting of frame R8i inverter modules, it may be possible to
continue operation even if a cooling fan of an inverter module stops. See the description
of the parameter.
Custom motor current fault limit (parameter 31.42)
The control program sets a motor current limit based on drive hardware. In most cases,
the default value is appropriate. However, a lower limit can be manually set by the user,
for example, to protect a permanent magnet motor from demagnetization.
Local control loss detection (parameter 49.05)
The parameter selects how the drive reacts to a control panel or PC tool communication
break.