EasyManua.ls Logo

ABB ACS880 - Fault Functions

ABB ACS880
646 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Configuration of external events; selection of behavior of
the drive upon fault situations.
Fault functions31
Inactive (true); DI6
(95.20 b8) / uint32
Defines the source of external event 1.
See also parameter 31.2 External event 1 type.
0 = Trigger event
External event 1
source
31.1
1 = Normal operation
00.Active (false)
11.Inactive (true)
2
DIIL input (10.2 DI delayed status, bit 15).
DIIL
3
Digital input DI1 (10.2 DI delayed status, bit 0).
DI1
4
Digital input DI2 (10.2 DI delayed status, bit 1).
DI2
5
Digital input DI3 (10.2 DI delayed status, bit 2).
DI3
6
Digital input DI4 (10.2 DI delayed status, bit 3).
DI4
7
Digital input DI5 (10.2 DI delayed status, bit 4).
DI5
8
Digital input DI6 (10.2 DI delayed status, bit 5).
DI6
11
Digital input/output DIO1 (11.2 DIO delayed status, bit 0).
DIO1
12
Digital input/output DIO2 (11.2 DIO delayed status, bit 1).
DIO2
See Terms and abbreviations (page 132).
Other
Fault (95.20 b8) /
uint16
Selects the type of external event 1.External event 1 type31.2
0The external event generates a fault.Fault
1The external event generates a warning.Warning
3If the drive is modulating, the external event generates a
fault.
Warning/Fault
Otherwise, the event generates a warning.
Inactive (true); DIIL
(95.20 b5) / uint32
Defines the source of external event 2. See also parameter
31.4 External event 2 type.
For the selections, see parameter 31.1 External event 1
source.
External event 2
source
31.3
Fault / uint16Selects the type of external event 2.External event 2 type31.4
0The external event generates a fault.Fault
1The external event generates a warning.Warning
3If the drive is modulating, the external event generates a
fault.
Warning/Fault
Otherwise, the event generates a warning.
Inactive (true) / uint32Defines the source of external event 3. See also parameter
31.6 External event 3 type.
External event 3
source
31.5
For the selections, see parameter 31.1 External event 1
source.
- / uint16Selects the type of external event 3.External event 3 type31.6
0The external event generates a fault.Fault
1The external event generates a warning.Warning
330 Parameters