Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Speed supervision settings; actual signal filtering; general
scaling settings.
Monitoring/scaling
settings
46
Note: The 16-bit scalings apply when parameter values
are read or written directly. With protocol- and
profile-specific read/write commands (eg. communication
objects), the scaling depends on the protocol or profile.
See the documentation of the adapter module.
1500.00; 1800.00 rpm
(95.20 b0) rpm / real32
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
Speed scaling46.1
23 Speed reference ramp). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter 30.12 Maximum speed).
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in
fieldbus, master/follower etc. communication.
1 = 1 rpm / 100 = 1
rpm
Acceleration/deceleration terminal/initial speed.0.10 ... 30000.00 rpm
50.00 Hz; 60.00 Hz
(95.20 b0) Hz / real32
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used
to define deceleration ramp rate (see parameter group 28
Frequency scaling46.2
Frequency reference chain). The frequency acceleration
and deceleration ramp times are therefore related to this
value (not to parameter 30.14 Maximum frequency).
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in fieldbus, master/follower etc. communication.
10 = 1 Hz / 100 = 1 HzAcceleration/deceleration terminal/initial frequency.0.10 ... 1000.00 Hz
100.0 % / real32Defines the 16-bit scaling of torque parameters. The value
of this parameter (in percent of nominal motor torque)
Torque scaling46.3
corresponds to 10000 in fieldbus, master/follower etc.
communication.
See also parameter 46.42 Torque decimals.
10 = 1 % / 10 = 1 %Torque corresponding to 10000 on fieldbus.0.1 ... 1000.0 %
1000.00 kW or hp /
real32
Defines the output power value that corresponds to 10000
in fieldbus, master/follower etc. communication. The unit
is selected by parameter 96.16 Unit selection.
Power scaling46.4
1 = 1 kW or hp / 100 =
1 kW or hp
Power corresponding to 10000 on fieldbus.0.10 ... 30000.00 kW
or hp
10000 A / real32Defines the 16-bit scaling of current parameters. The value
of this parameter corresponds to 10000 in fieldbus,
master/follower etc. communication.
Current scaling46.5
1 = 1 A / 1 = 1 ACurrent corresponding to 10000 on fieldbus.0...30000 A
0.00 rpm / real32Defines a speed corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
Speed ref zero
scaling
46.6
interface, or interface FBA A or FBA B). For example, with
a setting of 500, the fieldbus reference range of 0…20000
would correspond to a speed of 500…[46.1] rpm.
Note: This parameter is effective only with the ABB Drives
communication profile.
Parameters 403

Table of Contents