Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / uint32
When parameter 96.11 is set to User set I/O mode, selects
the user parameter set together with parameter 96.13 as
follows:
User parameter
set selected
Status of source
defined by 96.13
Status of source
defined by 96.12
Set 100
Set 201
Set 310
Set 411
User set I/O mode in196.12
00Not selected
11Selected
2
Digital input DI1 (10.2 DI delayed status, bit 0).
DI1
3
Digital input DI2 (10.2 DI delayed status, bit 1).
DI2
4
Digital input DI3 (10.2 DI delayed status, bit 2).
DI3
5
Digital input DI4 (10.2 DI delayed status, bit 3).
DI4
6
Digital input DI5 (10.2 DI delayed status, bit 4).
DI5
7
Digital input DI6 (10.2 DI delayed status, bit 5).
DI6
10
Digital input/output DIO1 (11.2 DIO delayed status, bit 0).
DIO1
11
Digital input/output DIO2 (11.2 DIO delayed status, bit 1).
DIO2
Source selection See Terms and abbreviations (page 132).
Other [bit]
Not selected / uint32
See parameter 96.12 User set I/O mode in1.
User set I/O mode in296.13
- / uint16Selects the unit of parameters indicating power,
temperature and torque.
Unit selection96.16
0 = kW
1 = hp
Power unitb0
Reservedb1
0 = C (°C)
1 = F (°F)
Temperature unitb2
Reservedb3
0 = Nm (N·m)
1 = lbft (lbf·ft)
Torque unitb4
Reservedb5…15
1 = 10000h…FFFFh
DDCS Controller /
uint16
Defines the 1st priority external source for synchronization
of the drive's time and date.
The date and time can also be directly set into
96.24 96.26 in which case this parameter is ignored.
Time sync primary
source
96.20
0No external source selected.Internal
1External controller.DDCS Controller
512 Parameters