Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Fieldbus communication configuration.Fieldbus adapter
(FBA)
50
See also chapter Fieldbus control through a fieldbus
adapter (page 609).
Disable / uint16Enables/disables communication between the drive and
fieldbus adapter A, and specifies the slot the adapter is
installed into.
FBA A enable50.1
Note: This parameter cannot be changed while the drive
is running.
0Communication between drive and fieldbus adapter A
disabled.
Disable
1Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 1.
Option slot 1
2Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 2.
Option slot 2
3Communication between drive and fieldbus adapter A
enabled. The adapter is in slot 3.
Option slot 3
No action / uint16Selects how the drive reacts upon a fieldbus
communication break. A time delay for the action can be
defined by parameter 50.3 FBA A comm loss t out.
FBA A comm loss
func
50.2
See also parameter 50.26 FBA A comm supervision force.
0No action taken.No action
1
Drive trips on 7510 FBA A communication. This only occurs
if control is expected from the FBA A interface (FBA A
Fault
selected as source of start/stop/reference in the currently
active control location), or if supervision is forced using
parameter 50.26 FBA A comm supervision force.
2
Drive generates an A7C1 FBA A communication warning
and freezes the speed to the level the drive was operating
Last speed
at. This only occurs if control is expected from the FBA A
interface, or if supervision is forced using parameter 50.26
FBA A comm supervision force.
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
Parameters 415