Selection of local and external control location sources and
operating modes.
Operation mode19
See also section Operating modes of the drive (page 26).
- / uint16Displays the operating mode currently used.
See parameters 19.1119.14.
Actual operation
mode
19.1
This parameter is read-only.
1None.Zero
2Speed control (in DTC motor control mode).Speed
3Torque control (in DTC motor control mode).Torque
4The torque selector is comparing the output of the speed
controller (25.1 Torque reference speed control) and torque
Min
reference (26.74 Torque ref ramp out) and the smaller of
the two is used.
5The torque selector is comparing the output of the speed
controller (25.1 Torque reference speed control) and torque
Max
reference (26.74 Torque ref ramp out) and the greater of
the two is used.
6The speed controller output is added to the torque
reference.
Add
7DC voltage control.Voltage
10Frequency control in scalar motor control mode.Scalar (Hz)
11Speed control in scalar motor control mode.Scalar (rpm)
20Motor is in magnetizing mode.Forced magn.
EXT1 / uint32Selects the source for external control location EXT1/EXT2
selection.
Ext1/Ext2 selection19.11
0 = EXT1
1 = EXT2
0EXT1 (permanently selected).EXT1
1EXT2 (permanently selected).EXT2
2Control word bit 11 received through fieldbus interface A.FBA A MCW bit 11
3
Digital input DI1 (10.2 DI delayed status, bit 0).
DI1
4
Digital input DI2 (10.2 DI delayed status, bit 1).
DI2
5
Digital input DI3 (10.2 DI delayed status, bit 2).
DI3
6
Digital input DI4 (10.2 DI delayed status, bit 3).
DI4
7
Digital input DI5 (10.2 DI delayed status, bit 4).
DI5
8
Digital input DI6 (10.2 DI delayed status, bit 5).
DI6
11
Digital input/output DIO1 (11.2 DIO delayed status, bit 0).
DIO1
12
Digital input/output DIO2 (11.2 DIO delayed status, bit 1).
DIO2
32Control word bit 11 received through the embedded fieldbus
interface.
EFB MCW bit 11
See Terms and abbreviations (page 132).
Other [bit]
238 Parameters