Control interfaces
■ Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA) input
by a jumper or switch on the control unit. Each input can be filtered, inverted and scaled.
The analog inputs on the control unit are read on a 0.5 ms time level.
The number of analog inputs can be increased by installing FIO-11 or FAIO-01 I/O
extensions (see Programmable I/O extensions below). The analog inputs on extension
modules are read on a 2 ms time level.
The drive can be set to perform an action (for example, to generate a warning or fault)
if the value of an analog input moves out of a predefined range.
Settings and diagnostics
Parameter group: 12 Standard AI (page 188).
Events: 80A0 AI Supervision (page 557) and A8A0 AI Supervised Warning (page 574).
■ Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Each output can be filtered,
inverted and scaled. The analog outputs on the control unit are updated on a 0.5 ms
time level.
The number of analog outputs can be increased by installing FIO-11 or FAIO-01 I/O
extensions (see Programmable I/O extensions below). The analog outputs on extension
modules are updated on a 2 ms time level.
Settings and diagnostics
Parameter group: 13 Standard AO (page 193).
■ Programmable digital inputs and outputs
The control unit has six digital inputs, a digital start interlock input, and two digital
input/outputs (I/O that can be set as either an input or an output). The digital inputs on
the control unit are read on a 0.5 ms time level.
One digital input (DI6) doubles as a PTC thermistor input. See section Motor thermal
protection (page 90).
Digital input/output DIO1 can be used as a frequency input, DIO2 as a frequency output.
The number of digital inputs/outputs can be increased by installing FIO-01, FIO-11 or
FDIO-01 I/O extensions (see Programmable I/O extensions below). The digital inputs
on extension modules are read on a 2 ms time level.
32 Program features