■ User lock
WARNING!
ABB will not be liable for damages or losses caused by the failure to activate the
user lock using a new pass code. See Cybersecurity disclaimer (page 19).
For improved cybersecurity, it is highly recommended that you set a master pass code
to prevent, for example, the changing of parameter values and/or the loading of firmware
and other files.
With several drives, set a unique pass code for each drive.
To activate the user lock for the first time,
•
Enter the default pass code, 10000000, into 96.2. This will make parameters
96.100…96.102 visible.
•
Enter a new pass code into 96.100. Always use eight digits; if using Drive Composer,
finish with Enter.
•
Confirm the new pass code in 96.101.
WARNING!
Store the pass code in a safe place – the user lock cannot be opened even
by ABB if the pass code is lost.
•
In 96.102, define the actions that you want to prevent (we recommend you select
all the actions unless otherwise required by the application).
•
Enter an invalid (random) pass code into 96.2.
•
Activate 96.8, or cycle the power to the control unit.
•
Check that parameters 96.100…96.102 are hidden. If they are not, enter another
random pass code into 96.2.
To reopen the lock, enter your pass code into 96.2. This will again make parameters
96.100…96.102 visible.
Settings and diagnostics
Parameters: 96.2 Pass code (page 508) and 96.100 Change user pass code…96.102
User lock functionality (page 517).
Events: A6B0 User lock open (page 565).
104 Program features