What to doCause
Event name /
Aux. code
Code
(hex)
Check the settings of the motor
configuration parameters in groups 98
and 99.
Nominal speed is higher than
synchronous speed with 1 pole pair.
3
Check that the drive is sized correctly
for the motor.
Check the settings of the motor
configuration parameters in groups 98
and 99.
Nominal current is outside limits.4
Check that the drive is sized correctly
for the motor.
Check the settings of the motor
configuration parameters in groups 98
and 99.
Nominal voltage is outside limits.5
Check that the drive is sized correctly
for the motor.
Check the settings of the motor
configuration parameters in groups 98
and 99.
Mechanical nominal power is higher
than electrical active power.
6
Check that the drive is sized correctly
for the motor.
Check the settings of the motor
configuration parameters in groups 98
and 99.
Nominal power not consistent with
nominal speed and torque.
7
Check that the drive is sized correctly
for the motor.
Check that all the required parameters
in group 99 have been set.
Parameters in group 99 have not been
set.
No motor dataA6A5
Note: It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
Set supply voltage in parameter 95.1
Supply voltage.
The supply voltage has not been defined.Supply voltage
unselected
A6A6
Close the user lock by entering an invalid
pass code in parameter 96.2 Pass code.
See section User lock (page 104).
The user lock is open, ie. user lock
configuration parameters
96.100…96.102 are visible.
User lock openA6B0
Confirm the new pass code by entering
the same code in 96.101. To cancel,
A new user pass code has been entered
in parameter 96.100 but not confirmed
in 96.101.
User pass
code not
confirmed
A6B1
close the user lock without confirming
the new code. See section User
lock (page 104).
Check PLC programming.The drive does not have a functionality
requested by a PLC, or requested
functionality has not been activated.
FBA A
parameter
conflict
A6D1
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 51 FBA A
settings.
Check PLC programming.The drive does not have a functionality
requested by a PLC, or requested
functionality has not been activated.
FBA B
Parameter
conflict
A6D2
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 54 FBA B
settings.
Check the reference source selection
parameters.
A reference source is simultaneously
connected to multiple parameters with
different units.
Reference
source
parametrization
A6DA