Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = 1New user pass code.10000000…99999999
- / uint32
(Visible when user lock is open)
Confirms the new user pass code entered in 96.100
Change user pass code (page 516).
Confirm user pass
code
96.101
1 = 1Confirmation of new user pass code.10000000…99999999
- / uint16
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by
the user lock. Note that the changes made take effect only
when the user lock is closed. See parameter 96.2 Pass
code.
Note: We recommend you select all the actions and
functionalities unless otherwise required by the application.
User lock functionality96.102
1 = ABB access levels (service, advanced programmer,
etc. [see 96.3]) disabled
Disable ABB access
levels
b0
1 = Changing the parameter lock state prevented, ie. pass
code 358 has no effect
Freeze parameter
lock state
b1
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• safety functions module (FSO-xx) configuration
• parameter restore
• loading an adaptive program
• loading and debugging an application program
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel
such as time/date formats and enabling/disabling
clock display.
Disable file downloadb2
1 = Access to parameters on disabled access levels from
fieldbus prevented
Disable FB write to
hidden
b3
Reservedb4…5
1 = Creating a backup and restoring from a backup
prevented
Protect APb6
1 = Bluetooth disabled on ACS-AP-W control panel. If the
drive is part of a panel bus, Bluetooth is disabled on all
panels.
Disable panel
bluetooth
b7
Reservedb8…10
1 = OEM access level 1 disabledDisable OEM access
level 1
b11
1 = OEM access level 2 disabledDisable OEM access
level 2
b12
Parameters 517