Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 / uint32Pass codes can be entered into this parameter to activate
further access levels (see parameter 96.3 Access levels
active) or to configure the user lock.
Entering "358" toggles the parameter lock, which prevents
the changing of all other parameters through the control
panel or the Drive Composer PC tool.
Entering the user pass code (by default, "10000000")
enables parameters 96.100 … 96.102, which can be used
to define a new user pass code and to select the actions
that are to be prevented.
Entering an invalid pass code will close the user lock if
open, i.e. hide parameters 96.100 … 96.102. After entering
the code, check that the parameters are in fact hidden. If
they are not, enter another (random) pass code.
Entering several invalid pass codes introduces a delay
before a new attempt can be made. Entering further invalid
codes will progressively lengthen the delay.
Note: You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a
safe place – the protection cannot be disabled even by
ABB if the code is lost.
See also section User lock (page 104).
Pass code96.2
1 = 1Pass code.0…99999999
- / uint16Shows which access levels have been activated by pass
codes entered into parameter 96.2 Pass code.
Note: This parameter is read-only.
Access levels active96.3
End user.End userb0
Service.Serviceb1
Advanced programmer.Advanced
programmer
b2
Reservedb3…10
OEM access level 1.OEM access level 1b11
OEM access level 2.OEM access level 2b12
OEM access level 3.OEM access level 3b13
Parameter lock.Parameter lockb14
Reservedb15
1 = 10000h…FFFFh
Done / uint16
Selects the application macro. See chapter Application
macros (page 111) for more information.
After a selection is made, the parameter reverts
automatically to Done.
Note: This parameter cannot be changed while the drive
is running.
Macro select96.4
0Macro selection complete; normal operation.Done
1
Factory macro (see 112).
Factory
2
Hand/Auto macro (see page 114).
Hand/Auto
508 Parameters