14.13.3.2 Configuring Modems
To configure a GSM or PSTN modem:
1. Scroll to MODEMS and press SELECT.
2. Toggle between PRIMARY and BACKUP for correct modem slot and press SELECT.
The ENABLE MODEM option is displayed.
3. ENABLE or DISABLE the modem as required.
4. Scroll to MODEM STATUS, SIGNAL LEVEL, TYPE, and FIRMWARE VERSION then press
SELECT to view details of the modem.
5. Configure the following modem settings from the menu as follows and press ENTER after each
selection:
Menu Option Description
COUNTRY CODE Select a country from the list.
GSM PIN (GSM modem only) Enter a GSM PIN for the SIM card.
ANSWER MODE Select to select the mode in which the modem answers incoming calls: NEVER
ANSWERS or ALWAYS ANSWERS.
ANSWER ENG.
ACC.
Select ENABLE to only answer when engineer access is granted.
SETUP SMS Select ENABLE SMS to enable SMS for this modem.
PSTN modem only
Select SMS SERVER to enter an appropriate phone number of the SMS service
provider that is accessible in your location, if required. This number automatically
displays the default number for SMS for the country selected.
To manually test SMS, select TEST SMS and enter the SMS NUMBER.
To automatically test SMS at specific time intervals, select
AUTOMATIC TEST, select a TEST INTERVAL and enter the SMS NUMBER.
PREFIX DIALLING PSTN modem only
Enter a prefix number to include before the SMS number, if required.
LINE MONITORING PSTN modem
Enable this feature to monitor the voltage of the line connected to the modem.
GSM Modem
Enable this feature to monitor the signal level from the GSM mast connected to the
modem.
MODE or TIMER
MODE - Select a monitoring MODE (DISABLED, ALWAYS ON, FULLSET). The
FULLSET option only enables this feature while the system is Fullset.
TIMER - Enter the number of seconds for the monitoring TIMER (0–9999 sec).
Note: EN 50131-9 Confirmation configuration
In order for EN50131-9 Confirmation to operate correctly, line monitoring must be
enabled. (See on page169.)
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the keypad