Line Status Information on the signal strength (GSM), or the status of the phone line (PSTN).
Incoming Calls Number count and (Duration)of incoming calls
Outgoing Calls Number count and (Duration)of outgoing calls
Incoming SMS Number count of incoming SMS
Outgoing SMS Number count of outgoing SMS
Failed Dial Attempts Number count of attempts to dial out that have failed.
15.11.1.5 Serial ports
The SPC controller provides a serial port (RS232) that offer the following functionality:
l
Logging of Events: The Serial port interface provides the ability to connect to a serial port on a
PC or a printer. With this connection, a terminal program can be configured to receive a log of
System Events or Access Events from the SPC controller.
l
System Information: The Serial port also provides an interface via a terminal program that
allows for the execution of a set of commands to interrogate the controller for specific system
information. This facility is available only as a tool for debug and information purposes and should
only be used by experienced installers.
To configure the serial ports:
l
Select Communications > Communications > Serial Ports.
The settings displayed will depend on the type of connection that the ports are used for. The
settings are described in the following sections.
15.11.2 FlexC
®
The SPC Flexible Secure Communications Protocol (FlexC) enables communications for an Internet
Protocol (IP) based single or multiple path Alarm Transmission System (ATS). An ATS is a reliable
communications link between a Supervised Premises Transceiver (SPT, for example, Ethernet
integrated onto the SPC panel) and a Receiving Centre Transceiver (RCT, for example, SPC Com XT or
the SPC Connect server, www.spcconnect.com). A FlexC ATS consists of a primary Alarm
Transmission Path (ATP) and up to nine backup Alarm Transmission Paths (ATPs). It enables:
l
two way transfer of data between the SPT, for example the SPC panel over Ethernet, and the
RCT, for example, the SPC Com XT server or the SPC Connect server, www.spcconnect.com.
l
Communication monitoring of a complete ATS and individual ATPs.
SPC intrusion panels support FlexC over IP with any of the following interfaces:
l
Ethernet
l
GSM modem with GPRS enabled
l
PSTN modem
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 215 I-200572