The configuration requirements for Authorised Setting are as follows:
l
Area Attributes:
Setting Authorisation
Set
Set and Unset (required for VdS)
Unset
l
Outputs:
Ready to set
Setting Ack
Fullset Done
l
Inputs
Keyarm
20.3 Locking Element
For VdS, it is mandatory to prevent entering a set area. This is done by using a Lock Element which is
mounted in the doorframe. The lock element consists of a small plastic bolt which locks the door in a
SET state. The position of the bolt is signaled by Lock element Lock or Lock element Unlock
outputs. This signal is checked during the setting process. If the “locked” information is not received,
the setting fails.
If a lock element is located within an area, the exit timer will be restricted to a minimum of 4 seconds
so that the lock element can be activated. When the exit timer reaches four seconds, the lock
element will be activated for three seconds. When the exit timer expires, the Lock Element input
must be in the closed state then the system will set.
If a lock element is opened during a set period it will be handled as an alarm zone.
If a lock element is closed during an unset process then it will be considered to be tampered and raise
a tamper on the zone.
If the lock element fails to open after the unlock signal is sent to the device, then a trouble will be
raised on that zone to signal that a mechanical failure has occurred.
If the Lock Element input (if configured) is not in the closed state when the exit timer expires, then
the system will not set and a Fail to Set signal will be raised. The Lock Element Unlock output will
be activated.