Delete a WRMT remote control
To delete a WRMT:
1. Go to Configuration > Hardware > Wireless > Transceiver list.
2. Click the Delete button beside the WRMT that you want to delete.
When you delete a WRMT from your system, you must also clear the internal registration in the
WRMT before you can re-use the WRMT.
To clear the internal registration:
l
On the WRMT, press and hold the PARTSET and UNSET buttons.
The LED blinks Red and Orange to confirm that registration is cleared.
15.10 Configuration
This section covers:
15.10.1 Configuring controller inputs and outputs 154
15.10.2 X-BUS 160
15.10.3 Changing system settings 169
15.10.4 Configuring zones, doors and areas 185
15.10.5 Calendars 197
15.10.6 Change own PIN 199
15.10.7 Configuring advanced settings 200
15.10.1 Configuring controller inputs and outputs
This section covers:
l
Editing an input below
l
Editing an output on the next page
l
Configuring system latch and auto set outputs on page159
15.10.1.1 Editing an input
1. Select Configuration > Hardware > Controller.
2. Configure the fields as described in the table below.
Input The number is presented for reference and can not be programmed.
End of Line Select the End of Line (EOL) for the zone input (default: 4K7).
Zone Number of the zone on the panel
Description Enter a text describing the input (max. 16 characters). This text will also
appear on the browser and keypad.
Type The type of zone (see Zone types on page278).
Area Only if (multiple) Areas is activated in menu Panel Settings > System
Settings > Options. Select the areas to which this zone has been
assigned.
Attributes An icon in this field indicates that attributes have been programmed for
this zone (see Input zones: attributes on the next page).
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser