4. Scroll to IP NETMASK.
5. Press SELECT and enter the IP NETMASK format XXX.XXX.XXX.XXX. (For single digits, leading
zero(s) are required, for example, 001.) When the ENTER key is operated, the system beeps
twice and states UPDATED if the IP NETMASK is valid.
6. Scroll to GATEWAY. Note the gateway needs to be programmed for access outside the network
(for use with the Portal).
7. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For single digits, leading
zero(s) are required, for example, 001.) When the ENTER key is operated, the system beeps
twice and states UPDATED if the GATEWAY is valid.
8. Scroll to DHCP. The DHCP is enabled if the LAN has a DHCP server to allocate the IP address.
The IP address is to be enabled manually. Note the gateway needs to be programmed if the panel
needs access outside the network (for Portal service).
9. Press SELECT and enter the GATEWAY format XXX.XXX.XXX.XXX. (For single digits, leading
zero(s) are required, for example, 001.)
When the ENTER key is operated, the system beeps twice and states UPDATED if the
GATEWAY is valid.
The DHCP option is displayed.
10. Toggle between DHCP ENABLED and DISABLED for preferred option.
11. Press SELECT.
14.13.3 Modems
The SPC system supports SPC intelli-modems (PSTN, GSM, GSM (4G)) for communications with
analogue lines and mobile network interfacing for enhanced communications and connectivity. The SPC
system must be configured accordingly.
14.13.3.1 Monitoring the transmission network interface
The SPC Alarm System sends a poll to SPC Com XT, which responds with a poll acknowledge (ACK).
On receipt of a valid poll ACK the SPC Alarm System updates its status to OK and resets its polling
interval timer (depending on the ATP category).
If the SPC Alarm System does not receive a polling ACK within the timeout (depends on ATP category),
the SPC Alarm System updates its status to DOWN.
SPC supports the following transmission interfaces:
l
Ethernet
l
GSM with GPRS enabled
GSM (4G)
l
PSTN modem.
NOTICE: Before changing PIN or new SIM card, ensure all power sources are disconnected (AC
mains and battery) or card will not be activated.
NOTICE: After a factory default, during the process of initial setup of the system with the keypad,
the panel detects if it has a primary or backup modem fitted, and if so, it displays its type and
automatically enables it (or them) with the default configuration. No other modem configuration is
allowed at this stage.
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the keypad
© Vanderbilt 2023 109 I-200572