14.13 Communication
1. Scroll to COMMUNICATION and press SELECT.
2. Scroll to the desired programming option.
14.13.1 Serial Ports
The serial ports allow older style PCs to be connected to the system or other peripheral equipment
like printers.
1. Scroll to SERIAL PORTS.
2. Press SELECT.
3. Scroll to the serial port to be programmed.
4. Select the desired programming option shown in the table below.
TYPE Determines if type is TERMINAL (system information) or PRINTER (SPC
event log).
BAUD RATE Determines the speed of the communication between the panel and the
peripheral equipment. Note that the baud rate must be set the same as
both items of equipment.
DATA BITS Determines the length of data packet to be transferred between the panel
and the peripheral equipment. Note that the data bits must be set the
same for both items of equipment.
STOP BITS Determines the number of stop bits at the end of the data packet. Note that
the stop bits must be set the same for both items of equipment.
PARITY Determines the parity (odd/even) of the data packet. Note that the parity
must be set the same for both items of equipment.
FLOW
CONTROL
Determines if the data is under hardware (RTS, CTS) or software control
(None). Note that the flow control must be set the same for both items of
equipment.
5. Press BACK to exit.
14.13.2 Ethernet Ports
To program the Ethernet port:
1. Scroll to ETHERNET PORT.
2. Press SELECT.
The IP ADDRESS option displays, XXX.XXX.XXX.XXX For single digits, leading zero(s) are
required, for example, 001.
3. Press SELECT and enter the preferred IP address.
When the ENTER key is operated, the system beeps twice and states UPDATED if the IP
address is valid. If the IP address is allocated manually, then this must be unique on the LAN or
VLAN, connected to panel. A value is not entered if the DCHP option is used.
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the keypad
© Vanderbilt 2023 108 I-200572