For more detail on X-BUS interfacing, see Wiring the X-BUS interface on page35.
15.10.2.5 Settings
To configure X-BUS connections:
1. Select Configuration > Hardware >X-BUS > X-Bus Settings.
2. Configure the fields as described in the table below.
Addressing
Mode
Select if expanders/keypads are either manually or automatically addressed
on the X-BUS.
X-BUS Type Select Loop or Spur configuration.
Retries The number of times the system attempts to re-transmit data on the X-BUS
interface before a communications fault is generated. (1–99: default is 25)
Comms
Timer
The length of time before a communication fault is recorded.
15.10.3 Changing system settings
This section covers:
l
Options below
l
Timers on page179
l
Identification on page183
l
Standards on page184
l
Clock on page184
l
Language on page185
15.10.3.1 Options
1. Select Configuration > System > System Options.
2. Configure the fields as described in the table below.
The options that are displayed vary depending on the Security Grade of the system.
Restriction System Option Description
General Settings
Areas Select to enable multiple areas on the system.
Note: This option is displayed for the Domestic and Commercial installation
types, only.
Code Restore Grade 3 only: A user, who does not have the right to restore an alarm, is able
to restore the alarm with this feature. On resetting an alarm, a 6 digit code is
required. The user must call the installer to generate a restore code, with
which the user is able to restore the alarm.
SPC42/52/53/63 Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 169 I-200572
08.12.2023