Delete Delete the selected calendar.
The calendar cannot be deleted if it is currently assigned to an SPC configuration item, that is,
zone, area, user profile, output, trigger, door or X-Bus component. A message is displayed
indicating the assigned item.
Global calendars created using SPC Manager cannot be deleted.
15.10.5.1 Adding/Editing a calendar
1. Select Configuration > Calendars > Add.
2. Provide a Description for the calendar (max. 16 characters).
Copying a Calendar
To make a copy of this calendar structure, click the Replicate button.
A new calendar is created with the same configuration as the original calendar. You can provide a
new description for the new calendar and edit the calendar configuration as required.
Week Types
Calendars are configured by assigning an optional Week Type for each calendar week. Up to three
Week Types may be defined for each calendar. Not all weeks must have a Week Type (that is, a
Week Type may be ‘None’). There is a system maximum number of 64 calendar configurations.
To configure a week type
1. Click Week Types.
2. Enter the desired times for setting/unsetting or for triggers. Use time guidelines for Automatic
Setting/Unsetting of Areas (see Automatic setting/unsetting of areas on the next page), or for
Automatic Setting/Unsetting of other Panel Operations (see Automatic setting/unsetting of
other panel operations on the next page).
Up to three week types may be configured.
3. Click Save and then Back.
4. Select the desired week type from the drop down menu for each of the required scheduled
weeks in the calendar.
5. Click Save.
6. Click Back.
See also
Automatic setting/unsetting of areas on the next page
Automatic setting/unsetting of other panel operations on the next page
Exceptions
Exceptions or exception days are used to configure automatic setting schedules for exceptional
circumstances outside of the normal weekly schedules defined in the calendars. Exceptions are
defined with a start and end date (day/month/year) and up to four on/off timing periods for different
panel operations including automatic setting/unsetting of areas or the switching on/off of triggers or
outputs. A maximum of 64 exceptions can be configured on the system.
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 198 I-200572