The peripheral firmware file is only stored temporarily in the file system. When a new peripheral
firmware file is uploaded, the current and new versions of the firmware for each peripheral and
modem is displayed.
l
Click the Upgrade button for the peripherals that require upgrading or click the Upgrade All
button to upgrade all peripherals.
If the firmware for a peripheral device in the pfw file is older than the existing firmware of that
device, a Downgrade button is available.
During upgrade, the panel checks if the firmware in the peripheral file supports the particular
hardware versions of the installed peripherals and does not allow an upgrade for those peripherals
which are not supported.
If the pfw file version differs from the controller version, a warning message is displayed
If the major version number of the firmware available for a device differs from the existing major
number of a device, a warning message is also displayed.
Upgrading the SPCP355.300 Smart PSU Firmware
To upgrade the SPCP355.300 Smart PSU you must ensure the following:
l
The mains power must be connected.
The upgrade procedure can take up to 2 minutes to complete. Do not perform any actions within
the browser, restart or shut down the system until the upgrade completes. A message will be
displayed when the process is complete.
See also
Adding/Editing User Profiles on page141
15.12.1.2 Upgrading Languages
A custom language file (*.clng) can be uploaded to the panel.
NOTICE: The panel must be licensed for use of custom languages and other languages.
To upgrade languages on the system:
1. Select File > Upgrade.
The Panel Upgrade Operations page is displayed.
2. Select the language file to upgrade by clicking the Browse button for the Language File
Upgrade option, selecting the required language file and then clicking on the appropriate
Upgrade button.
A list of available languages in this file is displayed.
3. Tick the box beside the language to be installed.
A maximum of 4 languages + English can be installed.
4. Click the Upgrade Selected button.
The Confirm Language Upgrade page is displayed showing any languages that are being
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 246 I-200572