1756-6.5.3 - December 1999
PLC-5C to Logix5550 Controller: Scheduled Communications 8-23
Verify the Message
1. Restore RSLogix5550.
2. Double-click on the Controller Tags folder in the Project window and
select the Monitor Tags tab.
3. Expand the PLC5_data tag.
In the PLC5_data.PLC5_data array you should see the data sent from
N10:0 and N10:1 incrementing once a second with an offset of 5.
This completes the PLC-5C to Logix5550 scheduled communications
example.
You should see these values
changing with an offset of 5.